Galaxy VX UPS Series
ECOnversion VFI-SS-111 Performance Verified per IEC62040-3
VFI-SS-111 assessment per IEC62040-3, “UNINTERRUPTIBLE POWER SYSTEMS (UPS) - PART 3: METHOD OF SPECIFYING THE PERFORMANCE AND TEST REQUIREMENTS” was conducted, yielding the following results: Conduct Input Dependency Characteristics: Output voltage +/- 10% and frequency +/-3% or +/-10% depending on EUT setup. Voltage Waveform Characteristics: Maximum measured harmonic distortion of 0.4% Dynamic Output Performance: The UPS output voltages remain within the limits of curve 1. Output – Non-linear Load: The UPS output voltages remain within the limits of curve 1. Dynamic Performance: The UPS output voltages remain within the limits of curve 1. Upstream Short Circuit: The UPS output voltages remain within the limits of curve 1.
UL Verification is an objective, science-based assessment that confirms the accuracy of marketing claims. Our independent assessment process scrutinizes the validity of specific advertising or promotional statements, giving you a way to separate verified fact from fiction.