Acoustic Nozzle for Inert Gas Fire Suppression System


Company:

Kidde-Fenwal, LLC

Verify ID:

V445408

Expiration date:

October 09, 2025 - October 08, 2026

Verification Mark

Product Information

Sound defusing nozzle that lowers the sound pressure level of total flooding Inert Gas Fire Suppression System discharges. The typical discharge for these systems tend to have a pronounced acoustic output, more than 110 dB measured at a 3 feet distance. The effect of these interactions could pose challenges for sound and vibration sensitive micro-mechanical systems. While lessening the adverse effects by moderating the sound pressure level to 110 dB or less, this acoustic nozzle offers one of the most extensive coverage areas and efficient radial throw discharges today, validated by accredited certification bodies for use in the Kidde Fire Systems Natura™ Inert Gas System. 

* This information was provided by Kidde-Fenwal, LLC and may contain additional information outside the scope of this Claim Verification.

Applicable To:

38-447075-XXX - ACOUSTIC NOZZLE - 3/4 NPT, 360 W/ORIFICE
38-447150-XXX - ACOUSTIC NOZZLE - 1-1/2 NPT 360 W/ORIFICE
38-457075-XXX - ACOUSTIC NOZZLE - 3/4 BSP, 360 W/ORIFICE
38-457150-XXX - ACOUSTIC NOZZLE – 1-1/2 BSP, 360 W/ORIFICE

Marketing Claim Verified by UL Solutions

1/3 octave sound pressure less than 110 dB at 3.3 ft (1 m) up to 3.03 lb/second (1.37 kg/second)

Verification Method

The Acoustic Nozzle was tested in accordance with ISO ANSI Standard S12.54-2011/ISO 3744:2010. IG-541 was tested as representative of IG-100, IG-55 and IG-01 inert gas fire suppression agents.

What is UL Verification?

UL Verification is an objective, science-based assessment that confirms the accuracy of marketing claims. Our independent assessment process scrutinizes the validity of specific advertising or promotional statements, giving you a way to separate verified fact from fiction.