Company:
Verify ID:
Expiration date:
* This information was provided by YAMATO PROTEC CORP and may contain additional information outside the scope of this Claim Verification.
Fire propagation suppressing film characteristics Verified per JSA S1011
Performance assessed per JSA-S1011:2022, Performance evaluation test of fire propagation suppressing film (FPS film) used in secondary lithium cell systems. The assessment was performed using cylindrical type cells with an energy density as follows: Volumetric energy density: 676 Wh/L Gravimetric energy density: 243 Wh/kg Average time for thermal runaway of the first adjacent cell without product installed = 194 seconds. No thermal runaway occurred in the adjacent cells with the product installed per the manufacturer's instructions.
UL Verification is an objective, science-based assessment that confirms the accuracy of marketing claims. Our independent assessment process scrutinizes the validity of specific advertising or promotional statements, giving you a way to separate verified fact from fiction.