Fire Pump Controller

Brand:
Master Control Systems Inc.
Verify ID:
A938126
Effective Date:
June 05, 2019 - June 04, 2020
Verification Mark
Product Information
The SIS modification to our standard fire pump controller Separates the existing Isolating Switch into a separate compartment with a bolted cover plate.  This allows the incoming power to be turned on or off at the fire pump controller without having to shut down the building due to the direct utility connection.  It also allows service to be done on the controller while energized without being exposed to unlimited energy.  Further, the PPE calories/cm²  has been UL verified and marked on the controller so the proper PPE clothe can be selected. 

* This information was provided by Master Control Systems Inc. and may contain additional information outside the scope of this Claim Verification.

Applicable To:
MCA, ECA, MCP, ECP, MCR, ECR, MCO, ECO, MCY, ECY, MCS, ECS, MCT, ECT, MCVA, ECVA, MCVR, ECVR, MCVS, ECVS, MCAT, ECAT, MCPT, ECPT, MCRT, ECRT, MCOT, ECOT, MCYT, ECYT, MCST, ECST, MCTT, ECTT, MCVAT, ECVAT, MCVRT, ECVRT, MCVST, ECVST

Marketing Claim Verified by UL

Incident Arc Energy available in fire pump controller cabinet is less than 0.5 cal/cm²

Verification Method

Incident Arc Energy was determined per the guidelines of UL RP 2986, Recommended Practice for Measuring Incident Energy Exposure

About the Manufacturer

Master is considered the innovator in the industry with it’s slogan “Leading the Way”. We were the first to put voltmeters in the door, the first to introduce variable speed for fire pumps, and the first to introduce maintenance safety with the new SIS modification.

What is UL Verification?