Company:
Verify ID:
Expiration date:
* This information was provided by NATIONAL FIRE FIGHTING MFG FZ CO and may contain additional information outside the scope of this Claim Verification.
FILMPLUS NF1-C6: Nominal 1 percent Aqueous Film Forming Foam, FILMPLUS NF3-C6: Nominal 3 percent Aqueous Film Forming Foam, FILMPLUS NF6-C6: Nominal 6 percent Aqueous Film Forming Foam, FILMPLUS AR (1X3)-C6: Nominal 1 or 3 percent Alcohol Resistant Aqueous Film Forming Foam, FILMPLUS AR (3X3)-C6: Nominal 3 percent Alcohol Resistant Aqueous Film Forming Foam, FILMPLUS AR (3X6)-C6: Nominal 3 or 6 percent Alcohol Resistant Aqueous Film Forming Foam
No PFOA/PFOS Detected
PFOA and PFOS testing: Quantity of PFOA is determined in liquid samples using the mass spectrometry (LC/MS/MS) test method entirely in accordance with SOP-ANL-28. Quantity of PFOS is determined in liquid samples using the mass spectrometry (LC/MS/MS) test method entirely in accordance with SOP-ANL-28. The Quantification limits are 1.65 µg/L for PFOA and 1.38 µg/L for PFOS. The quantitative test methods are based on restrictions on the marking and use of PFOS as identified in EU Directive 2006/122/EC, and on the dilution and extraction methods identified in DS/CEN/TS 15968: “Determination of extractable perfluorooctanesulphonate (PFOS) in coated and impregnated solid articles, liquids and firefighting foams - Method for sampling, extraction and analysis by LCqMS or LC-tandem/MS”
UL Verification is an objective, science-based assessment that confirms the accuracy of marketing claims. Our independent assessment process scrutinizes the validity of specific advertising or promotional statements, giving you a way to separate verified fact from fiction.